CALCULATORS
42 free planning calculators
UPS runtime, cooling load, PUE, generator sizing, fiber loss budget and more — each with its formula, inputs and assumptions on the page. No account, and they work offline.
Browse all calculators →
Default inputs: 1,000 W load · 4 × 12 V, 100 Ah batteries · 90% efficiency · 80% remaining capacity.
Usable energy (Wh) = battery-bank energy × (UPS efficiency % ÷ 100) × (remaining battery capacity % ÷ 100)
12 V × 100 Ah × 4 batteries × 1 strings = 4,800 Wh4,800 Wh × (90% ÷ 100) × (80% ÷ 100) = 3,456 Wh3,456 Wh ÷ 1,000 W = 3.46 h; rounded to the nearest minute = 3 h 27 minEvery result is an estimate for planning only—not a substitute for a licensed engineer’s design or manufacturer data.
LoadCairn started as a set of free planning calculators. It now covers the full loop: plan the facility, prepare for the certification, and study with people doing the same. Everything is free to start, and every method stays in view.
CALCULATORS
UPS runtime, cooling load, PUE, generator sizing, fiber loss budget and more — each with its formula, inputs and assumptions on the page. No account, and they work offline.
Browse all calculators →

EXAM PREP
BICSI, Cisco, CompTIA, Uptime and more. Every exam starts with a free 10-question sampler. Full banks run 500 questions with explanations and a timed mode set to the real exam's clock.
Try a free sampler →STUDY FORUM
Weekly practice threads with worked answers, channels for BICSI, Cisco and CompTIA, and a wall for score reports. No braindumps — we show the work.
Join the Study Forum →The toolkit / 42 calculators
Built for engineers, facility managers, technicians, MEP consultants, and students who want to inspect the reasoning—not just copy a number.
Not for: stamped construction documents, final equipment selection, or model-specific runtime guarantees. Use a licensed engineer and manufacturer data for those.
Browse all calculators
Estimate runtime from load, battery-bank configuration, UPS efficiency, and remaining capacity.
Read the UPS runtime calculator guideLOAD · BANK CONFIGURATION · EFFICIENCY · REMAINING CAPACITY
Plan rack power density and evaluate PDU capacity around the intended load.
RACK DENSITY · POWER · PDU CAPACITY
Enter circuit capacity and each equipment wattage to see total load, remaining headroom, and an over-capacity warning.
CIRCUIT CAPACITY · EQUIPMENT LOADS · TOTAL · REMAINING
Estimate standby generator kW and kVA requirements with running-load, power-factor, margin, and motor-start inputs.
RUNNING LOAD · POWER FACTOR · MARGIN · MOTOR START
Convert between kW, kVA and amps for single- and three-phase circuits, with power factor shown.
kW · kVA · AMPS · POWER FACTOR
Estimate diesel burn rate, runtime on a tank, and the tank size you need for a target runtime.
LOAD · FUEL RATE · TANK · TARGET RUNTIME
Work back from a target runtime to the watts each battery must deliver.
LOAD · RUNTIME · FACTORS · BATTERY DATASHEET
Convert battery voltage and nameplate amp-hour capacity to gross and usable energy, then estimate runtime at the entered load.
BATTERY VOLTAGE · CAPACITY · LOAD · DoD · EFFICIENCY
Estimate per-rack and facility energy and demand costs, including a 0.1 PUE savings comparison.
IT kW · RACKS · RATE · PUE · DEMAND CHARGE
Estimate demand load, required transformer capacity, standard size, and loading from transparent planning factors.
CONNECTED LOAD · DEMAND FACTOR · POWER FACTOR · GROWTH
Estimate three-phase capacitor correction, kVA freed, and line-current change from current and target power factor.
LOAD · CURRENT PF · TARGET PF · LINE VOLTAGE
Estimate motor starting kVA, three-phase current, and optional generator step load from motor HP, NEMA code, and starter planning factor.
MOTOR HP · NEMA CODE · STARTER · VOLTAGE · GENERATOR kVA
Estimate three-phase transformer available fault current and fault MVA from kVA, secondary voltage, and impedance.
TRANSFORMER kVA · SECONDARY V · %Z

Build a cooling-load estimate from IT demand, lighting, people, and the building envelope.
Read the cooling load formulas and assumptionsIT LOAD · LIGHTING · PEOPLE · ENVELOPE
Estimate sensible airflow in CFM from heat load and temperature rise.
SENSIBLE LOAD · TEMPERATURE RISE · AIRFLOW
Find dew point, relative humidity and grains of moisture, and check condensation margin against the ASHRAE recommended envelope.
TEMPERATURE · RELATIVE HUMIDITY · DEW POINT
Estimate ventilation humidification demand from outdoor and indoor design conditions, with a visible water-rate trace.
OUTSIDE-AIR FLOW · OUTDOOR DESIGN · INDOOR TARGET
Convert cooling load and ΔT into chilled-water flow.
COOLING LOAD · ΔT · FLOW · PIPE VELOCITY
Estimate required cooling units and compare N+1, N+2, and 2N using effective capacity after derating.
COOLING LOAD · RATED CAPACITY · DERATE · REDUNDANCY
Convert BTU/hr to refrigeration tons or tons to BTU/hr, with the conversion arithmetic and thermal kW equivalent shown.
BTU/HR · TONS · THERMAL kW
Convert full-load chiller efficiency among kW/ton, COP, and EER, with optional plant input power from cooling capacity.
kW/TON · COP · EER · CAPACITY
Estimate airflow through raised-floor perforated tiles and optional sensible cooling capacity from open area, velocity, and ΔT.
TILES · OPEN AREA · VELOCITY · ΔT
Estimate room air changes per hour from supply airflow and room volume, or calculate the airflow needed for a target ACH.
ROOM LENGTH · WIDTH · HEIGHT · SUPPLY CFM · TARGET ACH

Estimate single- or three-phase conductor voltage drop with copper or aluminum circular-mil data.
PHASE · VOLTAGE · CURRENT · MATERIAL · LENGTH
Compare cable cross-sectional area with estimated ladder and ventilated tray capacity.
TRAY WIDTH · CABLE DIAMETERS · QUANTITIES
Estimate raceway fill from NEC Table 4 dimensions and Table 5 conductor areas.
RACEWAY · TRADE SIZE · CONDUCTOR SIZE · COUNT
Plan duplex LC links, MPO trunk strand capacity, cassette count, spare links, and enclosure rack units.
LC LINKS · MPO TRUNK FIBERS · SPARE CAPACITY · CASSETTES · RU
Estimate switch-level PoE draw from IEEE 802.3 device counts, reserve headroom, and screen remaining capacity.
DEVICE CLASSES · SWITCH BUDGET · HEADROOM
Estimate cable boxes, keystone jacks, faceplates, 24-port patch panels, and patch cords from planned drops and run lengths.
DROPS · RUN LENGTH · SLACK · BOX SIZE

Estimate power usage effectiveness, data center infrastructure efficiency, and non-IT overhead from facility and IT power.
FACILITY POWER · IT POWER · PUE · DCiE
Turn nines into minutes of downtime and compare N, N+1 and 2N.
AVAILABILITY · DOWNTIME · REDUNDANCY
Estimate cost per outage and annual downtime cost from duration, cost rate, and incidents per year.
DURATION · COST RATE · INCIDENT FREQUENCY
Add up fiber, connector and splice loss and check it against 10G–100G limits.
Read the fiber loss formulas and assumptionsFIBER · CONNECTORS · SPLICES · CHANNEL LIMIT
Estimate annual site water use per unit of IT energy, with a gallon conversion and qualified industry-reference comparison.
SITE WATER · IT ENERGY · WUE · US GALLONS
Estimate annual electricity and diesel emissions with an editable grid factor and a visible CO2 calculation trace.
ELECTRICITY · GRID FACTOR · DIESEL · CO2e
Calculate the subnet mask, wildcard, network and broadcast addresses, address count, and usable range from an IPv4 address and CIDR prefix.
IPV4 ADDRESS · CIDR PREFIX · MASK · NETWORK · HOST RANGE

Compare average rack floor loading with a rated capacity using the rack’s rectangular footprint.
RACK WEIGHT · FOOTPRINT · FLOOR RATING
Estimate rack rows and positions from room dimensions, rack size, aisle widths, and perimeter clearance.
ROOM · RACK SIZE · AISLES · PERIMETER CLEARANCE
Estimate FK-5-1-12 or HFC-227ea quantity from room volume and minimum temperature with a visible NFPA 2001 total-flooding calculation.
ROOM LENGTH · WIDTH · HEIGHT · AGENT · CONCENTRATION · TEMP
Add rack height and planned equipment heights in U to see total planned space, remaining capacity, and any over-capacity condition.
RACK HEIGHT · EQUIPMENT HEIGHTS · PLANNED U · REMAINING U
Comparing tools? LoadCairn vs vendor UPS calculators · vs spreadsheets · vs generator sizing software
Install once, work anywhere
Install LoadCairn on your phone or laptop. The available calculators work offline, including floor loading and rack layout, so you can size a UPS or check a rack plan in an electrical room or basement with no signal.

A result you can review
Each calculation keeps its working in frame, so a planning estimate can be understood in context and checked against the source information that matters to your facility.
Every result is traceable to its formula and its published source (ASHRAE, NIST or manufacturer data), so you can defend the number in a design review.
The values and conditions behind the estimate stay visible.
See how the calculation is formed and where its method comes from.
Review the limits and assumptions before using the result for planning.
Every result is an estimate for planning only—not a substitute for a licensed engineer’s design or manufacturer data.
Calculator FAQsIndividual or team
Every calculator is free for individual, unsaved use. Paid plans add the tools to retain work, share it, and bring it into project records.
Included with paid plans
Your saved estimates stay yours: export them as CSV at any time. Read the privacy policy.
Contact LoadCairnEXAM PREP
Start with a free 10-question sampler for the exam you're facing — DCDC, RCDD, Installer 1, CCNA, Network+, Security+, CySA+ and 28 more. If the sampler finds gaps, the full practice bank for that exam is 500 questions with explanations, plus a timed mode that mirrors the real test. Samplers are free; full banks start at $29.