Review how the LoadCairn planning calculator compares total facility power with IT load, what its optional annual estimate assumes, and where the calculation stops.
Calculation method
Power inputs / planning only
- PUE = total facility power ÷ IT load
- DCiE (%) = IT load ÷ total facility power × 100 = 100 ÷ PUE
- Non-IT overhead (kW) = total facility power − IT load
PUE compares facility power, the numerator, with IT load, the denominator. In this calculator, DCiE is the reciprocal percentage calculation shown above; it is not a separate benchmark claim.
Illustrative example · not a target or industry benchmark
500 kW facility ÷ 400 kW IT = PUE 1.25
400 kW IT ÷ 500 kW facility × 100 = DCiE 80%
500 kW facility − 400 kW IT = 100 kW non-IT overhead
These match the calculator’s editable starting values and demonstrate the arithmetic only.
01 / Inputs and assumptions
Match the measurement basis
The calculator uses entered power values for a planning comparison. Its optional annual energy and cost estimates extend those inputs with fixed assumptions.
- Enter positive total facility power and IT load values in kW.
- Both power values should use the same measurement interval and facility/IT boundary.
- IT load cannot exceed total facility power.
- The optional annual energy estimate assumes facility power stays constant for 8,760 hours, with no leap-year adjustment.
- The optional annual cost multiplies that energy estimate by a constant, energy-only price per kWh.
02 / Limitations
A planning estimate, with boundaries
- The calculator cannot verify that the entered measurement intervals or meter boundaries match.
- A power-based calculation is not an energy-metered or audited annual PUE.
- The annual estimate does not model seasonal or load variation, demand charges, taxes, or other tariff terms.
- The result is not an engineering design, equipment-selection, or compliance result.
03 / Further reading
PUE source references
These references discuss PUE and its measurement. DCiE on this page is the calculator’s reciprocal calculation.
- The Green Grid, “PUE: A Comprehensive Examination of the Metric”
Defines PUE as an energy-based data center efficiency metric and describes measurement guidance.
- ENERGY STAR Portfolio Manager glossary: Data Center PUE
Describes data center PUE using total annual source energy divided by annual IT source energy.
04 / Run an estimate
Explore your own inputs
Adjust facility power and IT load in the browser, then review the calculation trace and planning assumptions.