All calculators
LoadCairn / Cooling airflow
Cooling airflow calculator
Estimate sensible cooling airflow from a heat load and temperature rise. The calculation runs in your browser and shows the coefficient and assumptions behind the result.
Live estimate
Rounded to the nearest whole CFM; the calculation retains its precision.
- Estimated airflow
- CFM
Before whole-CFM rounding (shown to 3 decimals): 462.963 CFM.
Inputs used
- Sensible heat load
- 10000 BTU/hr
- Temperature rise
- 20 °F
Formula and calculation trace
CFM = sensible heat load (BTU/hr) ÷ (1.08 × temperature rise (°F))
10000 ÷ (1.08 × 20) = 462.963 CFM
Assumptions and source
- The entered load is sensible heat only. Latent load from moisture is not calculated.
- The 1.08 BTU/(hr·CFM·°F) coefficient is a simplified dry-air sensible-heat factor at standard air conditions. ASHRAE shows the factor varies with humidity ratio (1.08 at W = 0; 1.10 at W = 0.01) and notes altitude correction for other elevations; this estimate applies no air-state or elevation correction.
- Reference: ASHRAE Handbook, Chapter 18 — Nonresidential Cooling and Heating Load Calculations. The source describes calculation methods and assumptions; it does not endorse this calculator.
Planning estimate only. This is not an engineered airflow design or an equipment rating.