LoadCairn / Power conversion guide

How to convert kW, kVA and amps

Equipment specs come in watts, panels are sized in amps, and UPS and generators are rated in kVA. Converting between them is simple once you know which voltage to use and where power factor fits. This guide covers the formulas for single-phase and three-phase power, with worked examples from real data center circuits.

01 / Power factor

kW vs kVA: power factor

kVA (apparent power) is voltage times current. kW (real power) is the part that does work. Power factor (PF) links them:

kW = kVA × PF

PF is between 0 and 1, so kW is never more than kVA. Modern IT power supplies with power-factor correction typically run around 0.95 or higher at normal load. Motors and older equipment are often lower. When you don't know the PF, use the equipment spec sheet rather than guessing.

02 / Single phase

Single-phase formulas

kVA = V × A ÷ 1,000

kW = V × A × PF ÷ 1,000

Amps = kW × 1,000 ÷ (V × PF)

03 / Three phase

Three-phase formulas

Use line-to-line voltage (e.g. 208 V or 480 V):

kVA = √3 × V × A ÷ 1,000

kW = √3 × V × A × PF ÷ 1,000

Amps = kW × 1,000 ÷ (√3 × V × PF)

(√3 ≈ 1.732, which comes from the 120° offset between phases.)

04 / Worked examples

Worked examples

  1. 1. A 100 kW load on a 480 V three-phase feed at 0.9 PF:

    kVA = 100 ÷ 0.9 = 111.1 kVA
    Amps = 100,000 ÷ (1.732 × 480 × 0.9) = 133.6 A per phase

  2. 2. A 5 kW rack on a 208 V single-phase circuit at 0.95 PF:

    kVA = 5 ÷ 0.95 = 5.26 kVA
    Amps = 5,000 ÷ (208 × 0.95) = 25.3 A

  3. 3. Capacity of a 208 V, 30 A three-phase PDU:

    kVA = 1.732 × 208 × 30 ÷ 1,000 = 10.8 kVA
    At 0.9 PF that's 9.7 kW, or about 7.8 kW if you plan to 80% of the rating.

05 / Review checklist

Common mistakes

06 / Design boundary

When to get a detailed design

These conversions are for planning and sanity checks. Conductor sizing, overcurrent protection, voltage drop and selective coordination need a licensed electrical engineer and the applicable code.

FAQ

Power conversion questions

Convert your numbers in the kW, kVA & amps calculator →

07 / Quick reference

kW, kVA and amps at a glance

kW is real power doing useful work. kVA is apparent power: the voltage and current capacity carried by the electrical source. Amps describe current flowing through a circuit. Power factor (PF) is the ratio of real power to apparent power; it accounts for how much of the supplied volt-ampere capacity becomes real power.

kW = kVA × power factor

Single-phase amps = kVA × 1,000 / V

Three-phase amps = kVA × 1,000 / (√3 × V)

For quick reference, this guide uses PF 0.8 for UPS nameplates and PF 0.9–1.0 for modern IT loads. Use the actual UPS, PDU, and equipment specifications or measured PF whenever available. Three-phase voltage in these equations is line-to-line voltage.

08 / Apparent power

kVA to amps

Line current for common apparent-power ratings. Three-phase values use line-to-line voltage and a balanced load; single-phase values use voltage across the load. Values are rounded to the nearest 0.1 A. On narrow screens, scroll horizontally to see all voltage columns.

kVA converted to amps at 208V three-phase, 480V three-phase, and 240V single-phase.
Rating (kVA)208V three-phase (A)480V three-phase (A)240V single-phase (A)
1027.812.041.7
2055.524.183.3
3083.336.1125.0
40111.048.1166.7
50138.860.1208.3
60166.572.2250.0
80222.196.2333.3
100277.6120.3416.7
125347.0150.4520.8
150416.4180.4625.0
200555.1240.6833.3
250693.9300.71041.7
300832.7360.81250.0
4001110.3481.11666.7
5001387.9601.42083.3

Formula: A = kVA × 1,000 / (√3 × V) for three-phase, or A = kVA × 1,000 / V for single-phase.

09 / Real power

kW to amps

This table assumes PF = 0.9 for every load at 208V balanced three-phase. It first converts kW to kVA (kVA = kW / 0.9), then calculates line current. Values are rounded to the nearest 0.1. On narrow screens, scroll horizontally to see all columns.

kW converted to equivalent kVA and amps at 208V three-phase, assuming power factor 0.9.
Load (kW)Equivalent kVA (PF 0.9)208V three-phase amps (PF 0.9)
55.615.4
1011.130.8
1516.746.3
2022.261.7
2527.877.1
3033.392.5
4044.4123.4
5055.6154.2

Formula: A = kW × 1,000 / (√3 × 208 × 0.9). Replace PF 0.9 with the actual equipment or measured value for a project calculation.

10 / Worked examples

Apply the conversions

100 kVA UPS output at 480V three-phase

  1. Use the three-phase kVA formula and line-to-line voltage.
  2. A = 100 × 1,000 / (√3 × 480)
  3. A = 100,000 / (1.73205 × 480) ≈ 120.3 A

The result is estimated line current for a balanced three-phase output; it is not a breaker or conductor recommendation.

30 kW rack at 208V three-phase, PF 0.9

  1. Convert real power to apparent power: kVA = kW / PF.
  2. kVA = 30 / 0.9 ≈ 33.3 kVA
  3. Use the three-phase kW formula for line current:
  4. A = 30 × 1,000 / (√3 × 208 × 0.9) ≈ 92.5 A

Both results assume a balanced three-phase load, 208V line-to-line, and PF 0.9.

Source formulas: Eaton, Basics of Power System Design, Table 68 and Schneider Electric, transformer kVA formula reference. The tables are calculations from the listed equations, rounded to 0.1; actual voltage, loading, PF, and manufacturer ratings can differ.

11 / Frequently asked questions

kW, kVA and amps questions