Equipment specs come in watts, panels are sized in amps, and UPS and generators are rated in kVA. Converting between them is simple once you know which voltage to use and where power factor fits. This guide covers the formulas for single-phase and three-phase power, with worked examples from real data center circuits.
kVA (apparent power) is voltage times current. kW (real power) is the part that does work. Power factor (PF) links them:
kW = kVA × PF
PF is between 0 and 1, so kW is never more than kVA. Modern IT power supplies with power-factor correction typically run around 0.95 or higher at normal load. Motors and older equipment are often lower. When you don't know the PF, use the equipment spec sheet rather than guessing.
02 / Single phase
Single-phase formulas
kVA = V × A ÷ 1,000
kW = V × A × PF ÷ 1,000
Amps = kW × 1,000 ÷ (V × PF)
03 / Three phase
Three-phase formulas
Use line-to-line voltage (e.g. 208 V or 480 V):
kVA = √3 × V × A ÷ 1,000
kW = √3 × V × A × PF ÷ 1,000
Amps = kW × 1,000 ÷ (√3 × V × PF)
(√3 ≈ 1.732, which comes from the 120° offset between phases.)
04 / Worked examples
Worked examples
1. A 100 kW load on a 480 V three-phase feed at 0.9 PF:
kVA = 100 ÷ 0.9 = 111.1 kVA Amps = 100,000 ÷ (1.732 × 480 × 0.9) = 133.6 A per phase
2. A 5 kW rack on a 208 V single-phase circuit at 0.95 PF:
kVA = 5 ÷ 0.95 = 5.26 kVA Amps = 5,000 ÷ (208 × 0.95) = 25.3 A
3. Capacity of a 208 V, 30 A three-phase PDU:
kVA = 1.732 × 208 × 30 ÷ 1,000 = 10.8 kVA At 0.9 PF that's 9.7 kW, or about 7.8 kW if you plan to 80% of the rating.
05 / Review checklist
Common mistakes
Using √3 on a single-phase circuit. In example 2, that would give 14.6 A instead of 25.3 A, undersizing the circuit by more than 40%.
Using line-to-neutral voltage with √3. For 100 kW at 0.9 PF on a 208Y/120 V system, plugging 120 V into the three-phase formula gives 534.6 A, nearly double the correct 308.6 A. Either use line-to-line voltage with √3, or use 3 × line-to-neutral voltage without it.
Treating kW and kVA as the same. A 100 kVA UPS is not a 100 kW UPS unless its output power factor is 1.0. Check the kW rating on the spec sheet.
Sizing to 100% of the breaker. The NEC generally requires circuits serving continuous loads to be sized at 125% of the load, which is where the common "plan to 80%" rule comes from. The 25.3 A rack in example 2 needs at least 31.6 A of capacity, so a 30 A circuit is too small. Confirm requirements with the code edition your jurisdiction has adopted and your AHJ.
06 / Design boundary
When to get a detailed design
These conversions are for planning and sanity checks. Conductor sizing, overcurrent protection, voltage drop and selective coordination need a licensed electrical engineer and the applicable code.
FAQ
Power conversion questions
Convert your numbers in the kW, kVA & amps calculator →
kW is real power doing useful work. kVA is apparent power: the voltage and current capacity carried by the electrical source. Amps describe current flowing through a circuit. Power factor (PF) is the ratio of real power to apparent power; it accounts for how much of the supplied volt-ampere capacity becomes real power.
kW = kVA × power factor
Single-phase amps = kVA × 1,000 / V
Three-phase amps = kVA × 1,000 / (√3 × V)
For quick reference, this guide uses PF 0.8 for UPS nameplates and PF 0.9–1.0 for modern IT loads. Use the actual UPS, PDU, and equipment specifications or measured PF whenever available. Three-phase voltage in these equations is line-to-line voltage.
08 / Apparent power
kVA to amps
Line current for common apparent-power ratings. Three-phase values use line-to-line voltage and a balanced load; single-phase values use voltage across the load. Values are rounded to the nearest 0.1 A. On narrow screens, scroll horizontally to see all voltage columns.
kVA converted to amps at 208V three-phase, 480V three-phase, and 240V single-phase.
Rating (kVA)
208V three-phase (A)
480V three-phase (A)
240V single-phase (A)
10
27.8
12.0
41.7
20
55.5
24.1
83.3
30
83.3
36.1
125.0
40
111.0
48.1
166.7
50
138.8
60.1
208.3
60
166.5
72.2
250.0
80
222.1
96.2
333.3
100
277.6
120.3
416.7
125
347.0
150.4
520.8
150
416.4
180.4
625.0
200
555.1
240.6
833.3
250
693.9
300.7
1041.7
300
832.7
360.8
1250.0
400
1110.3
481.1
1666.7
500
1387.9
601.4
2083.3
Formula: A = kVA × 1,000 / (√3 × V) for three-phase, or A = kVA × 1,000 / V for single-phase.
09 / Real power
kW to amps
This table assumes PF = 0.9 for every load at 208V balanced three-phase. It first converts kW to kVA (kVA = kW / 0.9), then calculates line current. Values are rounded to the nearest 0.1. On narrow screens, scroll horizontally to see all columns.
kW converted to equivalent kVA and amps at 208V three-phase, assuming power factor 0.9.
Load (kW)
Equivalent kVA (PF 0.9)
208V three-phase amps (PF 0.9)
5
5.6
15.4
10
11.1
30.8
15
16.7
46.3
20
22.2
61.7
25
27.8
77.1
30
33.3
92.5
40
44.4
123.4
50
55.6
154.2
Formula: A = kW × 1,000 / (√3 × 208 × 0.9). Replace PF 0.9 with the actual equipment or measured value for a project calculation.
10 / Worked examples
Apply the conversions
100 kVA UPS output at 480V three-phase
Use the three-phase kVA formula and line-to-line voltage.
A = 100 × 1,000 / (√3 × 480)
A = 100,000 / (1.73205 × 480) ≈ 120.3 A
The result is estimated line current for a balanced three-phase output; it is not a breaker or conductor recommendation.
30 kW rack at 208V three-phase, PF 0.9
Convert real power to apparent power: kVA = kW / PF.
kVA = 30 / 0.9 ≈ 33.3 kVA
Use the three-phase kW formula for line current:
A = 30 × 1,000 / (√3 × 208 × 0.9) ≈ 92.5 A
Both results assume a balanced three-phase load, 208V line-to-line, and PF 0.9.