All calculators

LoadCairn / Electrical planning

kW, kVA & amps calculator (single- and three-phase).

Convert real power, apparent power, voltage, current, and power factor with the phase assumptions and calculation shown alongside each estimate.

Read the guide: how to convert kW, kVA and amps →

Conversion inputs

Illustrative example · editable

The starting example is 5 kW, 208 V line-to-line, 0.90 PF, and balanced three phase. It calculates about 15.42 A. These example inputs are not a product rating or recommendation.

Choose the value to solve for from the other required values.

Uses F = √3, line-to-line voltage, and line current.

Select which known values the equation will use.

Enter real power for this load and operating point.

Use line-to-line RMS voltage for a balanced three-phase load.

Use a measured or equipment-specified power factor when available.

Planning estimate only

Calculated current

Current updated. The displayed estimate is rounded to two decimal places.

Current · planning only

15.42 A
Checking Pro access…Download kW-kVA-amps reportExport CSV

Estimates for planning only, not a substitute for a licensed engineer’s design or manufacturer data.

Calculation details

Selected equation

A = 1,000 × kW ÷ (√3 × VLL × PF)

Live calculation trace

A = 1,000 × 5 kW ÷ (1.732051 × 208 V × 0.9 PF) = 15.42068 A

Assumptions

  • Single-phase calculations use voltage across the load and current through that load. Balanced three-phase calculations use line-to-line voltage and line current, with F = √3.
  • Power factor is treated as the ratio kW ÷ kVA. For sinusoidal voltage and current, displacement power factor is cos φ; distorted waveforms can make total power factor differ from cos φ.
  • The entered voltage, current, power, and power factor describe the same operating point. The calculator does not infer missing equipment data.

Limitations

  • This simplified model does not account for phase imbalance, harmonics, voltage drop, efficiency, transient or motor-start current, or equipment-specific operating conditions.
  • It does not select conductors, protective devices, a transformer, a generator, or a PDU, and it does not establish code compliance or available capacity.
  • Confirm actual load data and installation conditions with equipment documentation and a qualified electrical professional before design or procurement.

Source notes

Schneider Electric Electrical Installation Guide: Definition of reactive power

Defines apparent and active power, relates PF to cos φ for sinusoidal signals, and lists single-phase and three-phase power relationships.

Schneider Electric: Single- and three-phase transformer kVA calculation

Gives single-phase kVA = V × I ÷ 1,000 and three-phase kVA = V × I × √3 ÷ 1,000, with related current calculations.

Planning estimate only. This result is not a substitute for licensed engineering design or manufacturer data. This simplified calculator is for early reference, not equipment selection, a safety determination, code compliance, or a guarantee. Verify the actual load and installation with a qualified electrical professional.

BICSI DCDC Study Guide and Practice Exam

Planning guide / kw-kva-amps

Introduction

The kW, kVA, and amps calculator converts between real power, apparent power, voltage, current, and power factor for a selected single-phase or balanced three-phase case. Use it to translate a documented load value into another electrical quantity for an early equipment or capacity discussion. The page requires a target and a defined input basis, then displays the formula and substituted values.

The starting example selects current as the target, real power as the basis, three-phase operation, 5 kW, 208 V line-to-line, and 0.90 power factor. Other target choices expose different input combinations, including kW from kVA and PF, kVA from voltage and current, or power factor from kW and kVA.

All entered values must describe the same load and operating point. The three-phase formulas assume a balanced load; power factor is treated as kW divided by kVA. The tool does not infer missing equipment data, phase imbalance, harmonics, efficiency, voltage drop, motor-start current, or code compliance.

Method / Calculation

How it works

Real power P is measured in kW and apparent power S in kVA. Power factor PF relates them as P = S × PF, so kVA = kW ÷ PF and kW = kVA × PF. When voltage and current are the basis, apparent power is voltage times current for single phase, or line-to-line voltage times line current times √3 for balanced three-phase, divided by 1,000 to convert VA to kVA.

Current from apparent power is kVA × 1,000 divided by voltage for single phase, or kVA × 1,000 divided by √3 and line-to-line voltage for balanced three-phase. Current from real power also divides by power factor. The corresponding voltage and power calculations are rearrangements of those same relationships.

The page uses the phase selector to choose the applicable factor and uses the selected basis to determine which values are required. It validates the power factor between greater than zero and one, and the result remains unavailable until the required values are valid. The trace shows the chosen formula and numerical substitution.

For sinusoidal voltage and current, displacement power factor is often represented by cos φ, but distorted waveforms can make total power factor differ from that relationship. A simple conversion is therefore only as appropriate as the supplied PF and the balanced-load assumption.

kW = kVA × PF; kVA = kW ÷ PF; PF = kW ÷ kVA

Single-phase kVA = V × A ÷ 1,000; single-phase A = kVA × 1,000 ÷ V

Balanced three-phase kVA = √3 × line-to-line V × line A ÷ 1,000

Balanced three-phase A from kW = kW × 1,000 ÷ (√3 × V × PF)

  1. Choose the target quantity the question asks for, such as current, kVA, or voltage. The target selection determines which other inputs are needed.
  2. Select the input basis that matches the values you have: real power and PF, apparent power and PF, or voltage and current. Do not combine values from different operating cases.
  3. Select single phase or balanced three phase. Use line-to-line voltage and line current for the three-phase case, and voltage across and current through the single-phase load for the single-phase case.
  4. Enter power factor as a decimal between zero and one. Use a measured or equipment-specified value when available rather than assuming unity.
  5. Read the formula trace, including phase factor, units, and substitution. Confirm the result units before comparing with ratings that may use a different basis.
  6. If the load is unbalanced or distorted, or a transient is important, use appropriate measurement and equipment data with a qualified electrical professional instead of extending this simplified conversion.

The calculator cites Schneider Electric’s Electrical Installation Guide for reactive-power definitions and its single- and three-phase transformer kVA FAQ for the power relationships shown. Those references support the page’s formula basis; the calculator does not claim that a selected equipment application is suitable.

Check the source values, voltage reference, phase configuration, and power-factor basis. A mathematically consistent conversion can still be the wrong planning input when the real load is unbalanced, nonlinear, transient, or measured at a different point in the system.

Use the conversion to make a stated set of electrical quantities comparable, not to make unlike nameplate values interchangeable. A kW value describes real power while kVA describes apparent power under the power-factor relationship used by the selected basis; current additionally depends on voltage and phase. If a source gives line current, confirm the corresponding voltage and whether the value is operating, rated, or a measured peak before entering it. A clean trace should let another reviewer reproduce the arithmetic and see every conversion factor rather than infer how a missing quantity was supplied.

For three-phase inputs, keep the line-to-line voltage and line current conventions consistent with the displayed equations. Do not insert phase-to-neutral voltage into a formula that expects line-to-line voltage, or combine a single-phase current with three-phase power. For single phase, use the voltage across that load and its matching current. The phase selector changes the equation, so comparing two runs is most useful when all other inputs and the target are held constant.

The power-factor field is a ratio, not a percentage entry. A lower entered PF increases the kVA or current calculated from a fixed real-power value, but this arithmetic does not say why that PF occurs or whether correction is appropriate. Nonlinear equipment, changing load, and measurement location may affect the source value. Use metering or manufacturer documentation that corresponds to the same operating condition, then evaluate circuit capacity, protection, harmonics, and equipment limits separately.

Keep the result attached to its source point in the distribution system. A value measured at a branch circuit, panel, transformer secondary, or service entrance may describe a different collection of loads, so the voltage, current, and power values should not be blended across boundaries. Likewise, the conversion does not include transformer losses or conductor impedance unless those effects are already reflected in the entered measurements. Label the target, phase, voltage basis, and PF source when sharing a result; that short record prevents a later reviewer from treating a valid arithmetic conversion as a complete system study.

This page does not calculate energy use over time, conductor ampacity, short-circuit duty, protective-device settings, or acceptable voltage variation. Those are separate questions with different inputs and applicable equipment data. If the output is being compared with a breaker, transformer, generator, or UPS rating, first confirm whether the rating is expressed in the same electrical quantity and under the same operating condition. Keep the original nameplate or measurement reference nearby so the result remains a traceable conversion rather than an isolated number.

Calculation trace / Illustrative inputs

Fully worked example

Illustrative calculation using the page’s default selection: find current from 5 kW real power at 208 V line-to-line, 0.90 PF, and balanced three-phase operation.

  1. Select the real-power basis and current target. The relevant relationship is I = P × 1,000 ÷ (√3 × V × PF).
  2. Convert real power: 5 kW × 1,000 = 5,000 W.
  3. Denominator = √3 × 208 V × 0.90 ≈ 324.04.
  4. Current = 5,000 ÷ 324.04 ≈ 15.42 A.

Illustrative calculator result: approximately 15.42 A for the selected 5 kW, 208 V, 0.90 PF, balanced three-phase inputs.

This example assumes a balanced three-phase load and consistent RMS values at one operating point. It does not account for harmonics, imbalance, efficiency, voltage drop, or transient current. Planning estimate only; verify the equipment and measurement basis.

Review / Input checks

Common mistakes

Questions / Planning use

Frequently asked questions

What is the difference between kW and kVA?

kW is real power and kVA is apparent power. This calculator relates them through entered power factor: kW equals kVA times PF, and kVA equals kW divided by PF.

Which voltage should I enter for three phase?

The page expects line-to-line RMS voltage for a balanced three-phase load, together with line current. Use the voltage reference specified by the equipment or measurement.

Should I enter 90 or 0.90 for power factor?

Enter 0.90 for a 90% power factor. The calculator validates a decimal greater than zero and no more than one.

Does the calculator account for harmonics or imbalance?

No. It states a balanced-load assumption for three phase and does not model phase imbalance, harmonics, voltage drop, efficiency, or transient current.

Which source basis is shown on the page?

It cites Schneider Electric’s Electrical Installation Guide for reactive power and its single- and three-phase transformer kVA calculation FAQ. The result still depends on valid project inputs and assumptions.

Continue / Related tools

Join the calculator waitlist