kW, kVA & Amps Calculator
Convert real power, apparent power, voltage, current, and power factor with the phase assumptions and calculation shown alongside each estimate.
Conversion inputs
Illustrative example · editable
The starting example is 5 kW, 208 V line-to-line, 0.90 PF, and balanced three phase. It calculates about 15.42 A. These example inputs are not a product rating or recommendation.
Choose the value to solve for from the other required values.
Uses F = √3, line-to-line voltage, and line current.
Select which known values the equation will use.
Enter real power for this load and operating point.
Use line-to-line RMS voltage for a balanced three-phase load.
Use a measured or equipment-specified power factor when available.
Planning estimate only
Calculated current
Current updated. The displayed estimate is rounded to two decimal places.
Current · planning only
Calculation details
Selected equation
A = 1,000 × kW ÷ (√3 × VLL × PF)
Live calculation trace
A = 1,000 × 5 kW ÷ (1.732051 × 208 V × 0.9 PF) = 15.42068 A
Assumptions
- Single-phase calculations use voltage across the load and current through that load. Balanced three-phase calculations use line-to-line voltage and line current, with F = √3.
- Power factor is treated as the ratio kW ÷ kVA. For sinusoidal voltage and current, displacement power factor is cos φ; distorted waveforms can make total power factor differ from cos φ.
- The entered voltage, current, power, and power factor describe the same operating point. The calculator does not infer missing equipment data.
Limitations
- This simplified model does not account for phase imbalance, harmonics, voltage drop, efficiency, transient or motor-start current, or equipment-specific operating conditions.
- It does not select conductors, protective devices, a transformer, a generator, or a PDU, and it does not establish code compliance or available capacity.
- Confirm actual load data and installation conditions with equipment documentation and a qualified electrical professional before design or procurement.
Source notes
Defines apparent and active power, relates PF to cos φ for sinusoidal signals, and lists single-phase and three-phase power relationships.
Gives single-phase kVA = V × I ÷ 1,000 and three-phase kVA = V × I × √3 ÷ 1,000, with related current calculations.
Planning estimate only. This simplified calculator is for early reference and is not engineering design, equipment selection, a safety determination, code compliance, or a guarantee. Verify the actual load and installation with a qualified electrical professional.