For data center engineers & facility managers · Vendor-neutral

Critical-facility planning, with the math in view.

Transparent planning calculators for critical facilities.

A mobile-friendly toolkit for twenty-nine critical-facility calculations, with the inputs and method behind each estimate in view.

Free. No account, no license server, no sales call.

UPS runtime / Cooling load / Rack power / PUE / Generator sizing / Cooling airflow / Dew point / kW / kVA / amps / Generator fuel burn & runtime / UPS battery sizing / Chilled water flow / Availability & downtime / Fiber loss budget

Works offline · Install as an app
Live calculation preview
Read-only sample

UPS runtime, with the math in view.

3 h 27 minplanning estimate

Default inputs: 1,000 W load · 4 × 12 V, 100 Ah batteries · 90% efficiency · 80% remaining capacity.

Usable energy (Wh) = battery-bank energy × (UPS efficiency % ÷ 100) × (remaining battery capacity % ÷ 100)

Current calculation

  1. 12 V × 100 Ah × 4 batteries × 1 strings = 4,800 Wh
  2. 4,800 Wh × (90% ÷ 100) × (80% ÷ 100) = 3,456 Wh
  3. 3,456 Wh ÷ 1,000 W = 3.46 h; rounded to the nearest minute = 3 h 27 min
Nominal bank energy
4,800 Wh
Usable energy after factors
3,456 Wh
Runtime in seconds
12,441.6 seconds

Assumptions and limits

  • The bank starts fully charged.
  • The load is constant real power measured in watts.
  • Series and parallel capacity arithmetic is ideal.
  • Nameplate Ah is treated as available energy before the explicit efficiency and remaining-capacity factors.
  • No chemistry-specific Peukert or discharge-rate curve is applied.
  • No temperature correction is applied.
  • No inverter cutoff, battery-management limit, power-factor or inrush behavior, or manufacturer calibration is modeled.

Every result is an estimate for planning only—not a substitute for a licensed engineer’s design or manufacturer data.

Open the UPS runtime calculator →

The toolkit / 29 calculators

Twenty-nine planning calculators. One clear method.

Built for engineers, facility managers, technicians, MEP consultants, and students who want to inspect the reasoning—not just copy a number.

Not for: stamped construction documents, final equipment selection, or model-specific runtime guarantees. Use a licensed engineer and manufacturer data for those.

Browse all calculators

Power & UPS

  1. 01

    UPS runtime

    Estimate runtime from load, battery-bank configuration, UPS efficiency, and remaining capacity.

    Read the UPS runtime calculator guide

    LOAD · BANK CONFIGURATION · EFFICIENCY · REMAINING CAPACITY

  2. 03

    Rack power

    Plan rack power density and evaluate PDU capacity around the intended load.

    RACK DENSITY · POWER · PDU CAPACITY

  3. 05

    Generator sizing

    Estimate standby generator kW and kVA requirements with running-load, power-factor, margin, and motor-start inputs.

    RUNNING LOAD · POWER FACTOR · MARGIN · MOTOR START

  4. 08

    kW / kVA / amps

    Convert between kW, kVA and amps for single- and three-phase circuits, with power factor shown.

    kW · kVA · AMPS · POWER FACTOR

  5. 09

    Generator fuel burn & runtime

    Estimate diesel burn rate, runtime on a tank, and the tank size you need for a target runtime.

    LOAD · FUEL RATE · TANK · TARGET RUNTIME

  6. 10

    UPS battery sizing

    Work back from a target runtime to the watts each battery must deliver.

    LOAD · RUNTIME · FACTORS · BATTERY DATASHEET

  7. 17

    Energy cost

    Estimate per-rack and facility energy and demand costs, including a 0.1 PUE savings comparison.

    IT kW · RACKS · RATE · PUE · DEMAND CHARGE

  8. 19

    Transformer sizing

    Estimate demand load, required transformer capacity, standard size, and loading from transparent planning factors.

    CONNECTED LOAD · DEMAND FACTOR · POWER FACTOR · GROWTH

  9. 23

    Power factor correction

    Estimate three-phase capacitor correction, kVA freed, and line-current change from current and target power factor.

    LOAD · CURRENT PF · TARGET PF · LINE VOLTAGE

  10. 26

    Motor starting & generator step load

    Estimate motor starting kVA, three-phase current, and optional generator step load from motor HP, NEMA code, and starter planning factor.

    MOTOR HP · NEMA CODE · STARTER · VOLTAGE · GENERATOR kVA

  11. 28

    Available fault current

    Estimate three-phase transformer available fault current and fault MVA from kVA, secondary voltage, and impedance.

    TRANSFORMER kVA · SECONDARY V · %Z

Cooling & Airflow

  1. 02

    Cooling load

    Build a cooling-load estimate from IT demand, lighting, people, and the building envelope.

    Read the cooling load formulas and assumptions

    IT LOAD · LIGHTING · PEOPLE · ENVELOPE

  2. 06

    Cooling airflow

    Estimate sensible airflow in CFM from heat load and temperature rise.

    SENSIBLE LOAD · TEMPERATURE RISE · AIRFLOW

  3. 07

    Dew point & humidity

    Find dew point, relative humidity and grains of moisture, and check condensation margin against the ASHRAE recommended envelope.

    TEMPERATURE · RELATIVE HUMIDITY · DEW POINT

  4. 29

    Humidification Load

    Estimate ventilation humidification demand from outdoor and indoor design conditions, with a visible water-rate trace.

    OUTSIDE-AIR FLOW · OUTDOOR DESIGN · INDOOR TARGET

  5. 11

    Chilled water flow (GPM)

    Convert cooling load and ΔT into chilled-water flow.

    COOLING LOAD · ΔT · FLOW · PIPE VELOCITY

  6. 18

    Cooling Unit Count & Redundancy

    Estimate required cooling units and compare N+1, N+2, and 2N using effective capacity after derating.

    COOLING LOAD · RATED CAPACITY · DERATE · REDUNDANCY

  7. 27

    BTU to Tons Cooling Converter

    Convert BTU/hr to refrigeration tons or tons to BTU/hr, with the conversion arithmetic and thermal kW equivalent shown.

    BTU/HR · TONS · THERMAL kW

Cabling

  1. 14

    Voltage drop

    Estimate single- or three-phase conductor voltage drop with copper or aluminum circular-mil data.

    PHASE · VOLTAGE · CURRENT · MATERIAL · LENGTH

  2. 15

    Cable tray fill

    Compare cable cross-sectional area with estimated ladder and ventilated tray capacity.

    TRAY WIDTH · CABLE DIAMETERS · QUANTITIES

  3. 16

    Conduit fill

    Estimate raceway fill from NEC Table 4 dimensions and Table 5 conductor areas.

    RACEWAY · TRADE SIZE · CONDUCTOR SIZE · COUNT

  4. 25

    MPO Fiber Breakout Planner

    Plan duplex LC links, MPO trunk strand capacity, cassette count, spare links, and enclosure rack units.

    LC LINKS · MPO TRUNK FIBERS · SPARE CAPACITY · CASSETTES · RU

Reliability & Network

  1. 04

    PUE

    Estimate power usage effectiveness, data center infrastructure efficiency, and non-IT overhead from facility and IT power.

    FACILITY POWER · IT POWER · PUE · DCiE

  2. 12

    Availability & downtime

    Turn nines into minutes of downtime and compare N, N+1 and 2N.

    AVAILABILITY · DOWNTIME · REDUNDANCY

  3. 13

    Fiber loss budget

    Add up fiber, connector and splice loss and check it against 10G–100G limits.

    Read the fiber loss formulas and assumptions

    FIBER · CONNECTORS · SPLICES · CHANNEL LIMIT

  4. 22

    WUE — Water Usage Effectiveness

    Estimate annual site water use per unit of IT energy, with a gallon conversion and qualified industry-reference comparison.

    SITE WATER · IT ENERGY · WUE · US GALLONS

Facilities & Space

  1. 20

    Floor loading

    Compare average rack floor loading with a rated capacity using the rack’s rectangular footprint.

    RACK WEIGHT · FOOTPRINT · FLOOR RATING

  2. 21

    Rack Layout & Floor Space Planner

    Estimate rack rows and positions from room dimensions, rack size, aisle widths, and perimeter clearance.

    ROOM · RACK SIZE · AISLES · PERIMETER CLEARANCE

  3. 24

    Clean-agent fire suppression quantity calculator

    Estimate FK-5-1-12 or HFC-227ea quantity from room volume and minimum temperature with a visible NFPA 2001 total-flooding calculation.

    ROOM LENGTH · WIDTH · HEIGHT · AGENT · CONCENTRATION · TEMP

Comparing tools? LoadCairn vs vendor UPS calculators · vs spreadsheets · vs generator sizing software

Install once, work anywhere

Take LoadCairn into the data hall

Install LoadCairn on your phone or laptop. The available calculators work offline, including floor loading and rack layout, so you can size a UPS or check a rack plan in an electrical room or basement with no signal.

  • Works offline: UPS runtime, UPS battery sizing, transformer sizing, available fault current, cooling load, cooling unit count and redundancy, airflow, dew point, humidification load, rack power, generator sizing, generator fuel burn, kW/kVA/amps, PUE, chilled water flow, availability, fiber loss budget, voltage drop, cable tray fill, conduit fill, MPO fiber breakout planning, energy cost, floor loading, rack layout, WUE water usage effectiveness, power factor correction, and clean-agent fire suppression quantity
  • Opens full-screen from your home screen, like a native app
  • Free, no app store, no account needed

A result you can review

No black-box numbers.

Each calculation keeps its working in frame, so a planning estimate can be understood in context and checked against the source information that matters to your facility.

Every result is traceable to its formula and its published source (ASHRAE, NIST or manufacturer data), so you can defend the number in a design review.

  1. 01 / TRACE

    Inputs

    The values and conditions behind the estimate stay visible.

  2. 02 / TRACE

    Formula + source

    See how the calculation is formed and where its method comes from.

  3. 03 / TRACE

    Assumptions

    Review the limits and assumptions before using the result for planning.

Planning estimate

Every result is an estimate for planning only—not a substitute for a licensed engineer’s design or manufacturer data.

Calculator FAQs

Individual or team

Calculate freely. Keep the work when you need to.

Every calculator is free for individual, unsaved use. Paid plans add the tools to retain work, share it, and bring it into project records.

Included with paid plans

  • Saved projects
  • Branded PDF reports
  • CSV exports
  • Shared team workspaces

Your saved estimates stay yours: export them as CSV at any time. Read the privacy policy.

Contact LoadCairn