Available fault current calculator

Enter transformer size, three-phase secondary voltage, and transformer impedance to see the supplied planning equations with each input and calculation step in view.

Inputs

Adjust the estimate

Results update as you change a value. Calculations run in this browser.

kVA
V
%Z

Live results

Current estimate

Full-load amps

—

Enter positive finite values for all three inputs.

Available fault current

—

Enter positive finite values for all three inputs.

Fault MVA

—

Enter positive finite values for all three inputs.

Formula and calculation trace

Full-load amps = kVA × 1000 / (√3 × V) · Available fault current = full-load amps / (%Z / 100) · Fault MVA = kVA / (%Z / 100) / 1000

Enter a transformer size, a positive three-phase secondary voltage, and a positive %Z.

Published source: Schneider Electric, FAQ FA105006 documents the three-phase full-load-current relation and transformer-secondary available-fault-current method.

Assumptions and limits

  • infinite bus on the primary (utility contribution and motor contribution excluded — both raise the real value); planning estimate for gear-rating discussions only, not an arc-flash or coordination study.

estimates for planning only, not a substitute for a licensed engineer's design or manufacturer data.