First, running apparent power is total real-power load divided by the entered power factor. A lower power factor therefore produces a larger kVA value for the same kW input. This conversion is a simplified steady-state representation and assumes the selected power factor describes the full entered running load.
Required kW multiplies total load by one plus the margin percentage divided by 100. Required kVA adds the optional motor-start allowance to running kVA and then applies the same margin factor. The page’s assumption is additive: it does not subtract the motor’s running demand from the total even if that motor may already be included there.
The calculator converts required kW into an equivalent 0.8-PF reference kVA by dividing by 0.80. It compares that number with required kVA and uses the larger value as the reference requirement. It then selects the first published value in its internal illustrative ladder that is greater than or equal to the reference requirement.
The ladder returns an example rating and a corresponding reference kW at 0.8 PF. It is not a catalog of current products or a promise that a specific rating is available. Manufacturer ratings, conditions, and selection practices must be confirmed for the site and load profile.
Running kVA = total running load kW ÷ load power factor
Margin factor = 1 + margin % ÷ 100; required kW = total kW × margin factor
Required kVA = (running kVA + optional motor-start kVA) × margin factor
Reference kVA = max(required kVA, required kW ÷ 0.80)
Reference size = first value in the calculator ladder ≥ reference kVA
- Sum the running real-power load for the scenario and enter that total in kW. Label whether it is measured, nameplate-based, or modeled peak demand.
- Enter a power factor that represents the same load condition. The calculator requires a value above zero and no more than one.
- Set the margin from the planning scenario. The page accepts zero through 100 percent; the margin is applied to both required kW and required kVA.
- Add a motor-start allowance only when the scenario calls for it. Treat it as an additive transient kVA allowance and note that the calculator does not remove the motor’s running load from total load.
- Read required kW, running kVA, and required kVA separately. Convert required kW to the 0.8-PF reference kVA and compare the two criteria.
- Use the rounded reference size as a discussion point only. Review the complete load schedule, starts, site conditions, generator rating basis, and manufacturer data before selecting equipment.
The page cites NFPA 110 context and manufacturer references as planning sources, while stating that the simplified formulas are not endorsed by those sources. Use the actual owner requirement, load profile, and published generator ratings in the engineering review.
The calculator’s additive motor allowance, 0.8 reference power factor, and internal size ladder are explicit assumptions. Preserve them in the scenario record so a reviewer can distinguish calculator arithmetic from the final design basis.
Compare required real power and apparent power as separate constraints. The reference size shown by the page is selected from its own size ladder after the calculator has applied the entered margin; that does not confirm a specific manufacturer model, voltage, enclosure, fuel system, altitude rating, or transient response. If the load has large motors, UPS rectifiers, transformers, or staged additions, capture those conditions in the load schedule and review how they affect both steady operation and starting events. The optional motor allowance is added to the apparent-power scenario; it is not a dynamic simulation and does not remove the motor from the running-load input.