Dew point & humidity calculator
Estimate dew point, vapor pressure, humidity ratio, and condensation risk from indoor air conditions. The calculation runs in your browser and screens an ASHRAE recommended envelope for data-center planning.
Live estimate
Results update with every valid input and unit change.
- Dew point
- Humidity ratio
- lb/lb
- Moisture content
- grains/lb
- Barometric pressure
- 101.325 kPa · 29.921 inHg
IN ENVELOPE
All recommended-envelope comparisons pass.
- Dry-bulb temperature 75.0°F is within the recommended 64.4°F to 80.6°F range.
- Dew point 52.2°F is within the recommended 15.8°F to 59.0°F range.
- Relative humidity 45% is at or below the recommended 60% maximum.
Calculation details
- Step 1: Gamma: γ = 17.625 × 23.888889°C ÷ (23.888889°C + 243.04) + ln(45 ÷ 100) = 0.778847
- Step 2: Dew point (Td): Td = 243.04 × 0.778847 ÷ (17.625 − 0.778847) = 11.236458 °C
- Step 3: Saturation vapor pressure (Psat): Psat = 0.61094 × exp(17.625 × 23.888889°C ÷ (23.888889°C + 243.04)) = 2.958252 kPa
- Step 4: Partial vapor pressure (Pw): Pw = (45 ÷ 100) × 2.958252 kPa = 1.331214 kPa
- Step 5: Barometric pressure (P): P = 101.325 × (1 − 2.25577e−5 × 0 m)^5.2559 = 101.325 kPa; 101.325 × 0.295299830714 = 29.921255 inHg
- Step 6: Humidity ratio (W): W = 0.621945 × 1.331214 kPa ÷ (101.325 kPa − 1.331214 kPa) = 0.00828
- Step 7: Humidity ratio (grains/lb): grains/lb = 0.00828 × 7000 = 57.959514 grains/lb
- Step 8: Dry-bulb temperature: 75.0°F within 64.4°F–80.6°F = PASS
- Step 9: Dew point: 52.2°F within 15.8°F–59.0°F = PASS
- Step 10: Relative humidity: 45% ≤ 60% = PASS
Assumptions and limits
- The Magnus approximation is accurate to about ±0.4°C between -40°C and 50°C.
- ASHRAE Thermal Guidelines (recommended envelope): dry bulb 64.4°F–80.6°F, dew point 15.8°F–59.0°F, and RH no more than 60%.
- Proposed TC 9.9 qualification — confirm with the owner: this recommended envelope is a planning reference for data-center IT equipment inlet conditions associated with ASHRAE TC 9.9 guidance; it does not replace equipment-manufacturer limits, project-specific psychrometric analysis, or a design review.
- Altitude adjusts barometric pressure and humidity ratio in this estimate; it does not adjust the dew-point calculation.
Planning estimate only. This is not a final design, an equipment rating, or a code-compliance determination.