All calculators

LoadCairn / Power & UPS

Power factor correction

Estimate the reactive power needed to move a three-phase load from its current power factor to a target. Inputs and each calculation stay visible.

Calculation inputs

Illustrative example · editable

The starting example is 500 kW at 480 V, three phase, with power factor moving from 0.85 to 0.95. It is an editable example, not a facility measurement.

Real load power; zero is allowed.

Use a measured or equipment-specified value when available.

A target no higher than the current PF requires no correction.

Three-phase line-to-line RMS voltage.

Live estimate

145.5 kVAR correction

Recommended capacitor bank: 150 kVAR

Step-by-step calculation

  1. tan θ₁ · current PF

    √(1 − PF₁²) / PF₁

    0.6197
  2. tan θ₂ · target PF

    √(1 − PF₂²) / PF₂

    0.3287
  3. Tangent difference

    tan θ₁ − tan θ₂

    0.2911
  4. Required correction

    kW × tangent difference

    145.5 kVAR
  5. Apparent power before → after

    kW / PF

    588.2 → 526.3 kVA
  6. Apparent power freed

    kVA before − kVA after

    61.9 kVA
  7. Three-phase line current before → after

    kVA × 1000 / (√3 × V)

    707.5 → 633.1 A
  8. Recommended capacitor bank

    Round correction UP to a 25 kVAR step

    150 kVAR

Formula and method

For each power factor, tan θ = √(1 − PF²) / PF. Required correction is load × (tan θ₁ − tan θ₂). Apparent power is kW / PF, and balanced three-phase line current is kVA × 1000 / (√3 × line voltage). The capacitor bank display rounds the calculated correction up to a 25 kVAR step.

Method reference: Eaton, Power factor correction: A guide for the plant engineer (2024). The guide states PF = kW / kVA, tan θ = kVAR / kW, and the three-phase line-current relation used here.

Assumptions and limits

  • Assumes a balanced three-phase load and line-to-line RMS voltage.
  • Holds real load power constant before and after correction.
  • Does not model harmonics, resonance, load variation, switching, protection, or voltage change.
  • The 25 kVAR step is a planning rounding rule, not a selected product or equipment recommendation.
  • Confirm measured conditions, capacitor suitability, and installation details with a licensed engineer and manufacturer data.
Open the DCDC hub

Planning guide / power-factor-correction

Introduction

The power factor correction calculator estimates the reactive power associated with moving a balanced three-phase load from its current power factor to a higher target. It uses real load power in kW, current and target power factor, and line-to-line RMS voltage. Its trace also compares apparent power and three-phase line current before and after the target change, then rounds the calculated correction upward to a 25 kVAR step for a planning bank-size display.

This estimate is useful for understanding how the entered power factors affect kVAR, kVA, and line current under the calculator’s assumptions. It can help organize questions for a facility review or compare a few hypothetical scenarios. The page’s editable starting values are examples, not a measured facility condition. Use measured or documented values when available and keep the source of those values with the calculation.

The calculation holds real load power constant and assumes a balanced three-phase load and line-to-line RMS voltage. It does not model harmonics, resonance, load variation, switching, protection, or voltage change. The displayed 25 kVAR increment is only a rounding rule in the calculator; it does not select a product or determine a suitable installation. Confirm suitability with the engineer and manufacturer data.

Method / Calculation

How it works

A power factor between zero and one can be expressed as the cosine of a phase angle. The calculator derives the tangent of that angle from PF, then multiplies the difference between the current and target tangent values by real load kW. When the target PF is no higher than the current value, the application reports no correction needed rather than a negative correction bank.

Apparent power before and after is calculated as real kW divided by the corresponding power factor. Under the balanced three-phase relationship used by the calculator, line current is kVA multiplied by 1,000 and divided by √3 times line-to-line voltage. The change in those values is an arithmetic comparison under fixed load power, not an independent measurement.

For a positive calculated kVAR correction, the bank display rounds upward to the next 25 kVAR increment. If the required correction is already at an increment, the displayed step remains there. The rounded bank value is distinct from the unrounded correction result; keep both visible when discussing a scenario.

tan θ = √(1 − PF²) / PF

Required kVAR = kW × (tan θ₁ − tan θ₂)

Apparent power = kW / PF; line current = kVA × 1,000 / (√3 × line-to-line volts)

Displayed bank step = correction rounded UP to the next 25 kVAR increment

  1. Enter real load power in kW, current power factor, target power factor, and three-phase line-to-line RMS voltage. Keep all inputs from one operating scenario and use the same measured or documented load basis.
  2. For the current PF and target PF separately, compute tan θ as the square root of one minus PF squared, divided by PF. The result is dimensionless.
  3. Subtract target tan θ₂ from current tan θ₁. Multiply that difference by load kW to obtain the unrounded correction in kVAR when the target PF is higher.
  4. Calculate apparent power before and after by dividing kW by current PF and target PF. Their difference is the change in kVA shown by the calculator.
  5. Convert each kVA value to three-phase line current by multiplying by 1,000 and dividing by √3 times line voltage. The same balanced-load and fixed-kW assumptions apply to both sides.
  6. Round a positive correction upward to the next 25 kVAR increment for the recommended-bank display. Treat that output as the calculator’s sizing step only, not as a selected capacitor product.

The existing method reference is Eaton’s “Power factor correction: A guide for the plant engineer” (2024), which the calculator cites for PF = kW / kVA, tan θ = kVAR / kW, and the three-phase line-current relation. Keep the supplied source visible with the arithmetic. A reference describes the method; it is not evidence that the example inputs represent a particular facility.

The limits are important when using the result. A real installation may require additional analysis for load behavior, harmonics, resonance, switching, protection coordination, voltage changes, and capacitor suitability. Those conditions are not captured by the page’s formula. The estimate is for discussion and planning, with actual conditions and manufacturer information reviewed separately.

Calculation trace / Illustrative inputs

Fully worked example

Illustrative example using the calculator’s current starting values: 500 kW, current PF 0.85, target PF 0.95, and 480 V three-phase line-to-line. These inputs are explicitly illustrative and are not a facility measurement.

  1. Current tangent = √(1 − 0.85²) ÷ 0.85 = about 0.6197. Target tangent = √(1 − 0.95²) ÷ 0.95 = about 0.3287.
  2. Tangent difference = 0.6197 − 0.3287 = about 0.2911. Required correction = 500 kW × 0.2911 = about 145.5 kVAR using unrounded tangent values.
  3. Apparent power before = 500 ÷ 0.85 = about 588.2 kVA. Apparent power after = 500 ÷ 0.95 = about 526.3 kVA. Difference = about 61.9 kVA.
  4. Current before = 588.2 × 1,000 ÷ (√3 × 480) = about 707.5 A. Current after = 526.3 × 1,000 ÷ (√3 × 480) = about 633.1 A.
  5. Round the positive 145.5 kVAR correction upward to a 25 kVAR step: 150 kVAR. This rounded bank value does not replace the separate correction, kVA, and current calculations.

Illustrative result: about 145.5 kVAR calculated correction, a 150 kVAR rounded bank step, 588.2 to 526.3 kVA, and 707.5 to 633.1 A.

All figures are arithmetic outputs for the stated example, not a facility measurement, savings claim, product selection, or installation instruction. The calculation holds real load constant and uses the balanced three-phase assumptions described above.

Review / Input checks

Common mistakes

Questions / Planning use

Frequently asked questions

What does the required kVAR value mean?

It is the arithmetic estimate kW times the difference between the current and target tan θ values when the target PF is higher. The calculator rounds that result upward to a separate 25 kVAR bank step. Both are planning outputs, not product selections.

Why does the calculator show both kVA and line current?

It calculates apparent power as kW divided by PF, then derives balanced three-phase line current from kVA, 1,000, √3, and line-to-line RMS voltage. The before-and-after comparison uses the same entered real load and voltage.

Is the 25 kVAR bank step a product recommendation?

No. It is the existing calculator’s upward rounding increment for a positive correction estimate. It does not select a product or determine capacitor suitability, switching, protection, resonance, or installation details.

What happens if the target PF is not higher?

When target power factor is less than or equal to current power factor, the calculator reports no correction needed and sets the correction and rounded bank value to zero. Confirm that both PF values describe the scenario you intend to compare.

Which source and assumptions apply to this calculation?

The calculator cites Eaton’s 2024 Power factor correction: A guide for the plant engineer. Its stated assumptions include a balanced three-phase load, line-to-line RMS voltage, and constant real power; it omits harmonics, resonance, variation, switching, protection, and voltage change.

Continue / Related tools