Air Changes Per Hour (ACH) Calculator

Estimate air changes per hour from room dimensions and supply airflow, or calculate the supply airflow needed for a target ACH.

Inputs

Adjust the estimate

Results update as you change a value. Calculations run in this browser.

ft
ft
ft
CFM
ACH

Illustrative sample inputs: 40 × 30 × 10 ft and 4,000 CFM. The target ACH starts at 20; edit values for the room being evaluated.

Calculated in this browser · No recalculation request · Works offline after load

Live results

Current estimate

Room volume

12,000 ft³

Length × width × height.

Air changes per hour

20.0 ACH

Supply airflow converted to hourly volume, divided by room volume.

Required supply airflow at target

4,000 CFM

For a target of 20 ACH.

Formula and calculation trace

Room volume (ft³) = length × width × height · ACH = supply CFM × 60 ÷ room volume · Required CFM = target ACH × room volume ÷ 60

  1. Room volume = 40 ft × 30 ft × 10 ft = 12,000 ft³.
  2. ACH = 4,000 CFM × 60 min/h ÷ 12,000 ft³ = 20.0 ACH.
  3. Required CFM = 20 ACH × 12,000 ft³ ÷ 60 min/h = 4,000 CFM.

Published source: CDC/NIOSH, Ventilation FAQs — air changes per hour calculation

Assumptions and limits

  • assumes well-mixed air; ACH is a planning figure for pressurization and purge estimates, not a substitute for CFD or a TAB report.

Estimates for planning only, not a substitute for a licensed engineer's design or manufacturer data.