Perforated Tile Airflow Estimator

Estimate airflow through raised-floor perforated tiles from tile count, open area, and face velocity. Enter supply/return ΔT to estimate sensible cooling capacity.

Inputs

Adjust the estimate

Results update as you change a value. Calculations run in this browser.

tiles
%
fpm
°F

Defaults to 20 °F. Clear the field to omit cooling capacity.

Live results

Current estimate

Airflow per tile

400 CFM/tile

Total airflow

4,000 CFM

Sensible cooling capacity

86,400 BTU/h

Sensible cooling power equivalent

25.3 kW

Formula and calculation trace

Tile face area = 4 ft² · Open area per tile = 4 × open-area % · CFM/tile = open area × velocity · Total CFM = CFM/tile × tiles · Cooling BTU/h = 1.08 × total CFM × ΔT · kW = BTU/h ÷ 3,412.14

  1. Tile face area = 24 in × 24 in / 144 = 4 ft².
  2. Open area per tile = 4 ft² × 25% / 100 = 1 ft².
  3. CFM per tile = 1 ft² × 400 fpm = 400 CFM/tile.
  4. Total CFM = 400 CFM/tile × 10 tiles = 4,000 CFM.
  5. Cooling BTU/h = 1.08 × 4,000 CFM × 20 °F = 86,400 BTU/h.
  6. Cooling kW = 86,400 BTU/h / 3412.14 = 25.3214 kW.

Published source: The ASHRAE Handbook, Chapter 18 describes the sensible heat equation and shows that its air factor varies with humidity ratio and altitude. This estimate uses the requested 1.08 factor and 24 in × 24 in tile face area.

Assumptions and limits

  • Assumes uniform plenum pressure and balanced dampers.
  • Real delivery varies with underfloor obstructions and tile placement.
  • Planning estimate.